Written by a journeyman licensed since 1999 for the open-book Texas Journeyman Electrician exam: two parts, 56 code questions in 130 minutes and 24 calculation questions in 110 minutes, 70% to pass each, 2026 NEC.

  • Study chapters on finding answers fast in the code book, set up for Texas book rules (soft-bound book, publisher tabs only)
  • Commercial and industrial math: motors, transformers, three-phase, feeders
  • Worked code math: box fill, voltage drop, conduit fill, ampacity, load calcs, EV charging
  • The Texas 210.8(F) amendment and how to answer it
  • Two timed Texas practice exams, one for each part, weighted to the PSI outline
  • Lifetime access for this code edition

Look inside

A worked example straight from the “Box Fill” chapter, exactly as it appears in the pack.

Worked example: the one you'll actually see

Here's a box I've wired a thousand times. Kitchen, 14-2 in and 14-2 out, one receptacle, metal device box with internal clamps.

What's in it:

  • 14-2 coming in: 1 hot, 1 neutral, 1 ground
  • 14-2 going out: 1 hot, 1 neutral, 1 ground
  • One duplex receptacle
  • Internal cable clamps
  • Grounds spliced with a pigtail to the device

Run the five categories:

1. Insulated conductors. Two hots and two neutrals = 4 conductors at #14.

4 × 2.00 = 8.00 cu in

(The grounds are not counted here — they get their own category. And the ground pigtail to the device is free, because it starts and ends in the box.)

2. Internal clamps. One allowance, largest conductor is #14.

1 × 2.00 = 2.00 cu in

3. Support fittings. None.

0.00 cu in

4. Device. One yoke, two allowances, #14 on the yoke.

2 × 2.00 = 4.00 cu in

5. Grounds. Two #14 EGCs — one single allowance.

1 × 2.00 = 2.00 cu in

Total required: 8.00 + 2.00 + 0.00 + 4.00 + 2.00 = 16.00 cu in

Now look at the box table. A 3" × 2" × 3½" device box is 18.0 cu in — that works. A 3" × 2" × 2¾" box is 14.0 cu in — that does not.

And that right there is why the deep boxes are worth carrying on the truck. A standard two-cable, one-device kitchen box needs 16 cubic inches and half the device boxes at the supply house don't have it.

What's inside

  1. 01Navigating the Code Book (Texas)
  2. 02The Texas Journeyman Electrician Exam
  3. 03Box FillRead it free
  4. 04Voltage Drop (Texas)
  5. 05Conduit Fill
  6. 06Ampacity (Texas)
  7. 07Residential Load Calculation (Texas)
  8. 08EV Charging (Texas)
  9. 09Journeyman Calculations: Motors, Transformers and Three-Phase
  10. 10Appendix — Preparing Your Code Book (Texas)
  11. 11Answers — Check Yourself (Texas)

Read online, or download every chapter as one PDF to print.

  • Texas Journeyman Practice Exam: NEC Knowledge · 56 questions · 130 minutes · Open book
  • Texas Journeyman Practice Exam: Calculations · 24 questions · 110 minutes · Open book